How to use Digital Operation
12.2.6
Initializing the user constant setting value
12
-24
7. Press the [DATA/ENTER] key to return to the auxiliary function execution mode dis-
play.
This completes the origin searching.
12.2.6 Initializing the user constant setting value
This function allows you to recover the standard setting (initial setting) even after changing
the user constants many times.
You must turn off the servo drive when activating this user constant initialization function .
To initialize the user constant, use the following procedure.
1. On the axis selection mode, select the axis you want to operate.
2. Press the [DSPL/SET] key and select the auxiliary function execution mode.
3. Select the user constant Fn005. Press the [LEFT] or [RIGHT] key to select the setting
digit. Press the [UP] or [DOWN] key until the value you want to set is displayed.
4. Press the [DATA/ENTER] key and the indication will display as below.
5. Press the [DSPL/SET] key. The new display like following initiates the user constant.
6. Press the [DATA/ENTER] key to return to the auxiliary function execution mode dis-
play.
This completes the initialization of user constant.
IMPORTANT
Flashes one
second.
Keep on flashing
while the initiation is
executed.
Stops
flashing.